Example: Advanced Simple I/O expansion using Xwire
Let’s consider a slightly more advanced example of SEXi operation. This time, we’ll use a DA8, which has 8 digital inputs, 6 digital outputs, 8 analogue inputs, and 2 analogue ouputs.
Master
By default, the Xwire Master script will look like this:
XWpMaster
;DA8, Address, 255=SEXi, 8 din, 6 dout, 8 ain, 2 aout
NV0Byte 0, 255, 8, 6, 8, 2, 0,0,0,0
NV0Byte 255 ; Terminate the scriptWhen this script is executed, the I/O for the DA8 simply gets added on to the end of the list for the master device. Firmware in the master takes care of tracking those I/Os. For example, if we have an HMI430 or HMI700, the I/O map will look something like this:
;-- digital inputs --
;all digital inputs are bi-directional, hence are shared with the digital outputs
iIp0 iEQU 0
iIp1 iEQU 1
iIp2 iEQU 2
iIp3 iEQU 3
iIp4 iEQU 4
iIp5 iEQU 5
iIp6 iEQU 6
iIp7 iEQU 7
;8 reserved
;-- DA8
iIn0 iEQU 9
iIn1 iEQU 10
iIn2 iEQU 11
iIn3 iEQU 12
iDipSw1 iEQU 13
iDipSw2 iEQU 14
iDipSw3 iEQU 15
iDipSw4 iEQU 16
;-- digital outputs --
;all digital outputs are bi-directional, hence are shared with the digital inputs
oOp0 oEQU 0
oOp1 oEQU 1
oOp2 oEQU 2
oOp3 oEQU 3
oOp4 oEQU 4
oOp5 oEQU 5
oOp6 oEQU 6
oOp7 oEQU 7
oBuzzer oEQU 8
;-- DA8
oOut0 oEQU 9
oOut1 oEQU 10
oOut2 oEQU 11
oOut3 oEQU 12
oLedOn oEQU 13
oLedGreen oEQU 14
;-- analogue inputs --
aiA EQU 0
aiB EQU 1
;-- DA8
aiIn0 EQU 2
aiIn1 EQU 3
aiIn2 EQU 4
aiIn3 EQU 5
aiIn4 EQU 6
aiIn5 EQU 7
aiIn6 EQU 8
aiIn7 EQU 9
;-- analogue outputs --
aoC EQU 0
;-- DA8
aoOut0 EQU 1
aoOut1 EQU 2Slave
Surprisingly, the firmware in the slave end doesn’t handle SEXi. Instead, we have to build the code ourselves. This is what’s running in a task on the DA8 by default:
taskSEXI:
;Xwire communications lost, turn off all outputs
LoadX 0
LoadX %00001111
OutputM 0 ;digital 0 thru 3
fLoadW 0.0
fAnOut 0
fAnOut 1
SetMem XWbOutput0_7,0
SetMem XWbBlink0_7,0
fStore XWfAnalogOut0
fStore XWfAnalogOut1
Off oLedGreen ;signal we have..
On oLedOn ;..no connection
SetMem XWbInputSeq,0 ;setup start up synchronisation
SetMem XWbInputSeqEcho,255
SetS XWsWafEqual
_XWWafFirstPacket
MarkTime ;start the interface toggle timer
_XWWafFirstPacketLoop
YieldTask
GoIfMz XWbInputSeqEcho,_XWGotConnection ;wait for master's first output update
LoopIfTiming 100,_XWWafFirstPacketLoop ;waf 1 second
GoSub subTogglePhys ;try the other interface
Goto _XWWafFirstPacket ;restart the timer
_XWGotConnection
On oLedGreen ;signal we are now..
On oLedOn ;..connected
_XWSendInputs
;-- capture latches
LoadX %00001111 ;capture rising edge flags, but not the DIP switches
InputMK 0
Store XWbInputK0_7
RecallS XWsWafEqual ;TRUE if this is the first packet
StoreS XWiSlaveOK,XWbInputK0_7 ;set slave ok latch if this is the first pass
;-- capture digital inputs
InputM 0 ;capture debounced input levels
LoadX %00001111 ;filter off the..
AndM ;..DIP switches
Store XWbInputs0_7
SetS XWiSlaveOK,XWbInputs0_7 ;keep slave ok input active
;-- capture analogue inputs
fAnIn 0 ;pass latest analogue values to the master
fStore XWfAnalogIn0
fAnIn 1
fStore XWfAnalogIn1
fAnIn 2
fStore XWfAnalogIn2
fAnIn 3
fStore XWfAnalogIn3
fAnIn 4
fStore XWfAnalogIn4
fAnIn 5
fStore XWfAnalogIn5
fAnIn 6
fStore XWfAnalogIn6
fAnIn 7
fStore XWfAnalogIn7
Recall XWbInputSeq ;increment the sEQUence number but avoid zero
IncX
Push
GoIfnz _XWStoreSeq
IncX
_XWStoreSeq
Store XWbInputSeq
XwireGetPollCntr ;reset the poll counter
MarkTime
_XWWafNewPacket
YieldTask
Recall XWbInputSeqEcho ;get the seq number echoed back from the master
GoIfST XWsWafEqual,_XWChkEqual ;for the first packet, we await sync
XwireGetPollCntr ;have we been polled by the master?
GoIfZ _XWChkEqual ;jump if not, wait for master to echo our sEQUence number back to us
IncX ;owise, we'll allow the master's seq number to be one behind ours
Push ;but skip..
GoIfnz _XWChkEqual
IncX ;..zero
_XWChkEqual
Recall XWbInputSeq ;get our seq number
Compare
GoIfz _XWHandleNewPacket ;jump if the sequence numbers match (or we've been polled and it's one behind)
LoopIfTiming XWkErrorTime,_XWWafNewPacket ;check for Xwire communication error
Goto taskSEXI ;owise comms lost, outputs off and re-synchronise
_XWHandleNewPacket
ClrS XWsWafEqual ;now we've been polled, we'll allow our sync to be one ahead for speed
;--echo digital outputs
Recall XWbOutput0_7 ;update outputs if not being blinked
Recall XWbBlink0_7
NotM
LoadX %00001111 ;only update..
AndM ;..the 4 outputs (not the LED)
OutputM 0
;--echo blink
Recall XWbBlink0_7 ;update blink outputs
LoadX %00001111 ;only update..
AndM ;..the 4 outputs (not the LED)
BlinkM 0
;--echo analogue outputs
fRecallW XWfAnalogOut0 ;update the analogue outputs
fAnOut 0
fRecallW XWfAnalogOut1
fAnOut 1
Goto _XWSendInputs
...
XWpSlave
NV0Byte XWabInputBuffer,XWkInputlen,XWabOutputBuffer,XWkOutputLenThe memory blocks are defined this way:
XWkInputLen #EQU 35
XWabInputBuffer defBLOCK XWkInputLen
XWbInputSeq defBYTE
XWbInputs0_7 defBYTE
XWbInputK0_7 defBYTE
XWiSlaveOK #EQU 4
XWfAnalogIn0 defFLOAT
XWfAnalogIn1 defFLOAT
XWfAnalogIn2 defFLOAT
XWfAnalogIn3 defFLOAT
XWfAnalogIn4 defFLOAT
XWfAnalogIn5 defFLOAT
XWfAnalogIn6 defFLOAT
XWfAnalogIn7 defFLOAT
XWkOutputLen #EQU 11
XWabOutputBuffer defBLOCK XWkOutputLen
XWbInputSeqEcho defBYTE
XWbOutput0_7 defBYTE
XWbBlink0_7 defBYTE
XWfAnalogOut0 defFLOAT
XWfAnalogOut1 defFLOATNote that the LEDs are explicitly NOT controlled by the master. Similarly, the DIP switches are not sent. You can, in fact, omit these from the Xwire map and it will still work. If you do, of course, you’ll need to remove them from the I/O map as well.
Digital Inputs and Outputs Beyond the First 8
The DA8 has less than 8 inputs and less than 8 outputs. What happens if the device has more? For example, a DM16 or D T16?
Easy, just duplicate the Inputs and/or Outputs sections. Here’s the memory allocation for a DM16:
XWkInputLen #EQU 13
XWabInputBuffer defBLOCK XWkInputLen
XWbInputSeq defBYTE
XWbInputs0_7 defBYTE
XWbInputs8_15 defBYTE
XWbInputK0_7 defBYTE
XWbInputK8_15 defBYTE
XWfAnalogIn0 defFLOAT
XWfAnalogIn1 defFLOAT
XWkOutputLen #EQU 21
XWabOutputBuffer defBLOCK XWkOutputLen
XWbInputSeqEcho defBYTE
XWbOutput0_7 defBYTE
XWbOutput8_15 defBYTE
XWbBlink0_7 defBYTE
XWbBlink8_15 defBYTE
XWfAnalogOut0 defFLOAT
XWfAnalogDOut7 defFLOAT
XWfAnalogDOut8 defFLOAT
XWfAnalogDOut9 defFLOATYou can see that each element is duplicated in turn: The “XWbInputs” lines, followed by the matching “XWbInputK” lines (which report changes of states); then the “XWbOutput” lines and the “XWbBlink” lines. The code is duplicated as well.
Virtual Outputs and Inputs
By extending this code, it’s also possible to add extra virtual outputs and inputs to do other functions. For example, a board such as a DA8 usually has at least one or two serial ports available, which can be used as Modbus masters (for example) to read sensors, and/or to control actuators. The results of these sensors can be reported as additional “virtual” inputs (digital or analogue). The actuators can be controlled using additional “virtual” outputs.
A very common “virtual” input is a a “Slave OK” input. Similarly, a very common “virtual” output is a “Master OK” output. If Xwire stops working for some reason (such as the wire being unplugged or breaking), the firmware will turn these signals off.
Memory Transfer
Now, you may have noticed that “0,0,0,0” at the end of the Master script near the top of this page. What’s that all about, then?
These are for memory transfer. The first two numbers are the address (in the master) and length of memory to be sent to the slave, and the second are the address (in the master) and length of memory to be sent from the slave to the master. Here’s an example of a Master script that receives some state and fault code from a modified DA8:
XWkHPStateLen EQU 2
XWpHpState mEQU 156,XWkHPStateLen
XWbHpMainState mEQU 156,1
XWbHpFaultCode mEQU 157,1
...
XWpMaster
;DA8, 8 din, 9 dout, 12 ain, 4 aout
NV0Byte 0, 255, 8, 9, 12, 4, 0,0,XWpHpState,XWkHPStateLen ; DA8
NV0Byte 255This particular DA8 also has some extra virtual inputs and outputs.
At the other end (the DA8 in this case), these extra bits of memory are simply tacked onto the end of the memory block for the Xwire transfer:
XWkInputLen #EQU 53
XWabInputBuffer defBLOCK XWkInputLen
XWbInputSeq defBYTE
XWbInputs0_7 defBYTE
XWbInputK0_7 defBYTE ; For changes of state
XWiSlaveOK #EQU 4
XWiHeatPumpOK #EQU 5
XWfAnalogIn0 defFLOAT
XWfAnalogIn1 defFLOAT
XWfAnalogIn2 defFLOAT
XWfAnalogIn3 defFLOAT
XWfAnalogIn4 defFLOAT
XWfAnalogIn5 defFLOAT
XWfAnalogIn6 defFLOAT
XWfAnalogIn7 defFLOAT
XWfTankTemp defFLOAT ; Temperatures read from the heat pump
XWfDefrostTemp defFLOAT
XWfHotSP defFLOAT ; Setpoints read from the heat pump
XWfColdSP defFLOAT
XWbMainState defBYTE
XWbFaultCode defBYTEYou can also see where the additional inputs are added.
Caveats